Описание

  • Usage up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • Control using safety relays
  • 3 redundant safety contacts
  • 1 auxiliary contact (monitoring contact)
  • Earth fault/ground fault monitoring can be selected
Relay outputsThe outputs are electrically decoupled and of redundant design. ConnectionBy using suitable wiring the following function can be selected:
  • Earth fault/ground fault monitoring to detect short circuits between the connection cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Dimension drawing Wiring diagram Dimension drawingWiring diagram Technical dataApprovals Mechanical values and environment
Housing material Polyamide PA6.6
Weight
Net 0,23 kg
Ambient temperature
At UB = 115/230V AC -15 ... 40 °C
Degree of protection IP20
Mechanical life
operating cycles 10 x 106
Contact material AgNi-10
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Connection Connection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Auxiliary contacts S23/S24
Number of auxiliary contacts 1
Safety contacts 13/14, 23/24, 33/34
Number of safety contacts 3
Electrical connection ratings
Operating voltage
AC 115 V -10% ... +10%
Power consumption (apparent power)
At 230 V AC 3,5 VA
Rated insulation voltage Ui 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Overvoltage category according to IEC EN 60664-1 3
Rated supply frequency 50 ... 60 Hz
Degree of contamination (external, according to EN 60947-1) 2
Connection cross-section 0,14 ... 2,5 mm? Connection terminal (size)
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S11 24 V
Control current
S11...S14 40 mA
LED indicator 2 status displays (green) for relays K1 and K2
Auxiliary contacts S23/S24
Type of output
NC As monitoring contact for safety relay
Safety contacts 13/14, 23/24, 33/34
Type of output
NO Relay contacts, positively driven (redundant)
Switching voltage
AC max.250 V
DC max.24 V
Switching current min.20 mA at 24V
Cumulative current max.10,5 A For all contacts
Fusing
External contact fuses (safety circuit) according to IEC 60269-1 10A gG (T4A / F6A)
Utilization category according to EN 60947-5-1
AC-15 4A, 250V
DC-13 2A, 24V
AC-12 6A ohmic load, 250V
DC-12 1.25A ohmic load, 24V
Breaking capacity according to UL 6A 250V AC / 2A 24V DC per contact
Other
In compliance with EN 60439-1: 1999 + A1: 2004, EN 60947-1: 2007, EN 60947-5-1: 2004, EN 60947-7-1: 2002, EN 61000-6-2: 2005, EN 61000-6-3: 2007, EN ISO 13849-1: 2015, EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015, EN 60204-1: 2007
Reliability values according to EN ISO 13849-1
Performance Level PL e
Category 4
PFHD 1.2 x 10-8
Number of switching cycles
? 2 A at 24 V DC max.17000 1/Jahr
? 0.1 A at 24 V DC max.400000 1/Jahr
? 1 A at 24 V DC max.73000 1/Jahr
Mission time 20 y
''